Designing Wastewater Treatment Systems and Studying the Sewage Absorption Coefficient in Temperate Regions of Iran

Publish Year: 1394
نوع سند: مقاله کنفرانسی
زبان: English
View: 622

This Paper With 8 Page And PDF Format Ready To Download

  • Certificate
  • من نویسنده این مقاله هستم

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این Paper:

شناسه ملی سند علمی:

ICOAC01_137

تاریخ نمایه سازی: 9 مرداد 1395

Abstract:

Background & Objective: Determination of quantitative and qualitative specifications of raw wastewater entering the wastewater treatment systems is one of the main elements of their correct design. This study aims to determine the parameters of designing wastewater treatment systems and study their sewage absorption coefficient for temperate regions of the country. Method of Study: In this descriptive – analytical study, two anaerobic and aerobicwastewater treatment systems located in Guilan Province were selected as a pilot in a temperate region and the qualitative and quantitative specifications of the wastewater entering them were investigated in the study period. In addition to the continuous measurement of thewastewater discharge into the system, temperature, PH, chemical oxygen demand (COD), 5- day biochemical oxygen demand (BOD5), and total suspended solids (TSS) were measured in 24-hour compound samples. Findings: The average per capita of parameters under research in this study based on milligrams per liter with industrial-domestic use for every day of production of BOD5, COD and TSS was equal to 90, 346.5 and 59.8 L, respectively and the average production ofindustrial wastewater was 16000 L per day. By comparing the results of per capita parametersin two wastewater treatment systems, a significant difference was determined between BOD5, COD and TSS parameters.Conclusion: Using the designing parameters specific for developed countries for designing awastewater treatment system and absorbing the resulting sewage in cities of Iran is not appropriate. Therefore, it is suggested to use the designing parameters based on different weather conditions and real specifications of wastewaters for increasing the efficiency in theoperation of wastewater treatment systems. Thus, the application of a unit design as anintegrated system can separately reduce the pollution load of each industrial wastewater to the level of environmental standards, and significantly reduces the need for the design andimplementation of a collection network and wastewater treatments. This is more important when the underground aquifers’ level is close to the ground level (temperate and cold regions) and not only the administrative problems resulted from these underground networks, but also the pollution risk of these aquifers is considered.

Authors

Hamidreza Ansari Joveini

Lecturer in the Department of Civil Engineering, ShahidChamranFaculty of Engineering in Rasht

Mohammad Ansari Joveini

Master of Science in Civil Engineering, Road & Transportation - Deputy Chairman of the Board of Directors in GhaemsazanAfra Co.

Mahdi Ansari Joveini

Master of Science in Civil Engineering, Structure - Chairman of the Board of Directorsin GhaemsazanAfra Co.

Mohadeseh Ansari Joveini

Bachelor of Science in Architectural Engineering, Member of the Board of Directors in GhaemsazanAfra Co.

مراجع و منابع این Paper:

لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :
  • Archival SJ. Wastewater treatment for pollution control. New Deihli: McGraw ...
  • Metcalf Eddy. Wastewater engineering treatment disposal and reuse. 4 ed. ...
  • Determination of design parameters for designing municipal wastewater treatments, Journal ...
  • Research review of wastewater pollutants in Tehran wastewater treatment, AliakbarAzi ...
  • نمایش کامل مراجع