CIVILICA We Respect the Science
(ناشر تخصصی کنفرانسهای کشور / شماره مجوز انتشارات از وزارت فرهنگ و ارشاد اسلامی: ۸۹۷۱)

Investigation of Energy Performance Improvement in a Natural Gas Compressor Stations via Reduce Compressed Gas Temperature through Heat Pipes

عنوان مقاله: Investigation of Energy Performance Improvement in a Natural Gas Compressor Stations via Reduce Compressed Gas Temperature through Heat Pipes
شناسه ملی مقاله: JR_GPJU-8-2_003
منتشر شده در در سال 1399
مشخصات نویسندگان مقاله:

Araz Alizadeh - Phd Student, Department of Natural Resources and Environment, Science and Research Branch, Islamic Azad University, Tehran, Iran
Mohammad Behshad Shafiee - Professor, School of Mechanical Engineering, Sharif University of Technology, Tehran, Iran
Seyyed Alireza Mirzahosseini - Assistant Professor, Department of Natural Resources and Environment, Science and Research Branch, Islamic Azad University, Tehran, Iran
Abtin Ataei - Assistant Professor, Department of Natural Resources and Environment, Science and Research Branch, Islamic Azad University, Tehran, Iran

خلاصه مقاله:
Natural gas compressor stations in gas transmission industries cause to increase gas pressure and discharge to gas transmission pipeline. Air coolers in compressor station, have high electrical energy consumption and pressure drop. In this investigation, the application of heat pipe heat exchangers (HPHE) in a case study of the gas compressor station is evaluated to use instead of air coolers. The result of the investigation shows that applying ۶۲۰ heat pipes with a ۵۰% filling ratio, working fluid R۱۳۴ and arranged triangularly, can reduce the compressed natural gas temperature. Energy performance analysis shows that using this method improves total, thermal, and electrical energy performance indicators (۳%, ۲.۴ %, and ۷۸%, respectively). Also simulating process demonstrate that using HPHE cause to save ۱,۱۱۵,۰۰۰ SCM fuel in gas turbine and ۳,۸۰۰ MWh electrical saving in air coolers. In addition, results show with using HPHE ۲,۶۱۵,۰۰۰ $ cost saving is available and project payback period value less than ۱ year evaluated, and avoiding ۱۶۵۲ ton CO۲ emission estimated annually.

کلمات کلیدی:
Energy performance, Natural gas Cooling, Heat pipe

صفحه اختصاصی مقاله و دریافت فایل کامل: https://civilica.com/doc/1134176/