A Complete Excitation-Shaft-Bearing Model to Overcome The Shaft Induced Voltage And Bearing Current
عنوان مقاله: A Complete Excitation-Shaft-Bearing Model to Overcome The Shaft Induced Voltage And Bearing Current
شناسه ملی مقاله: PEDSTC02_037
منتشر شده در دومین کنفرانس بین المللی الکترونیک قدرت و سیستم های درایو در سال 1389
شناسه ملی مقاله: PEDSTC02_037
منتشر شده در دومین کنفرانس بین المللی الکترونیک قدرت و سیستم های درایو در سال 1389
مشخصات نویسندگان مقاله:
reza Kazemi Golkhandan - Department of Electrical Engineering K. N. Toosi University of Technology Tehran,Iran
mohammad Tavakoli Bina - Department of Electrical Engineering K. N. Toosi University of Technology Tehran,Iran
masoud Aliakbar Golkar - Department of Electrical Engineering K. N. Toosi University of Technology Tehran,Iran
mohsen jokar - MAPNA E&C Co.(MECO) Karaj,Iran
خلاصه مقاله:
reza Kazemi Golkhandan - Department of Electrical Engineering K. N. Toosi University of Technology Tehran,Iran
mohammad Tavakoli Bina - Department of Electrical Engineering K. N. Toosi University of Technology Tehran,Iran
masoud Aliakbar Golkar - Department of Electrical Engineering K. N. Toosi University of Technology Tehran,Iran
mohsen jokar - MAPNA E&C Co.(MECO) Karaj,Iran
This paper proposes a complete distributed model for investigating the induced shaft voltage and bearing current in turbo generators due to the interaction with the static excitation systems. This undesirable voltage affects the insulations gradually, lowering the life expectancy of the whole system. If the shaft voltage exceeds the dielectric breakdown voltage level of the lubricating grease film in journal bearings, an electrical discharge current flows through the bearings. In order to inspect the shaft voltage, a passive filter is proposed to overcome the stated issue. Both the proposed model and the passive filtering technique are simulated with SIMULINK, and discussed in detail to confirm the presence of the bearing current and shaft voltage.
کلمات کلیدی: bearing current, breakdown voltage, passive filter, shaft voltage, static excitation system
صفحه اختصاصی مقاله و دریافت فایل کامل: https://civilica.com/doc/152850/