A New Wide Area Islanding Protection Scheme By Using PMU
Publish place: 27th International Power System Conference
Publish Year: 1391
نوع سند: مقاله کنفرانسی
زبان: English
View: 2,357
This Paper With 7 Page And PDF Format Ready To Download
- Certificate
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
PSC27_002
تاریخ نمایه سازی: 19 دی 1391
Abstract:
This paper presents a new wide area islanding protection method with negligible non-detection zone (NDZ). The Principle of the proposed method is based on the absolute variation and difference of positive sequence voltage angles (PSVA) measured by PMUs, at the DG terminal bus and the closest bus to the DG. The new technique is suitable for using in wide area protection and measurement technology. This newly proposed technique has been verified by using the radial distribution network including a wind turbine equipped with a squirrel-cage induction generator (SCIG). The simulations are done in SIMULINK/MATLAB software.
Keywords:
wide area islanding protection , islanding detection , phasor measurement unit , non-detection zone , positive sequence voltage angles
Authors