CIVILICA We Respect the Science
(ناشر تخصصی کنفرانسهای کشور / شماره مجوز انتشارات از وزارت فرهنگ و ارشاد اسلامی: ۸۹۷۱)

Investigation of Chlorine Gas Emission Hazards at ABFA Chlorination Plant at Abadan Station using Aloha and Marplot Software

عنوان مقاله: Investigation of Chlorine Gas Emission Hazards at ABFA Chlorination Plant at Abadan Station using Aloha and Marplot Software
شناسه ملی مقاله: JR_IJRRS-6-1_002
منتشر شده در در سال 1402
مشخصات نویسندگان مقاله:

Dariush Nouribakhsh - Abadan Faculty of Petroleum Engineering, Petroleum University of Technology, Abadan, Iran
Gholamreza Rashed - Department of Technical Inspection Engineering, Petroleum University of Technology, Abadan, Iran

خلاصه مقاله:
Chlorine is a toxic and oxidizing gas used in Iran to purify drinking water, and failure to control the effects of a gas leak or tank explosion could cause irreparable harm to workers and residents around the station. There has been no research on this issue in the city of Abadan. This research investigated the release of chlorine gas from a ۱۰۰۰-liter tank at ۱ tonne and ۱.۵ tonnes at the Abadan Chlorination Station. Aloha software was used to investigate the rate of diffusion, different risk areas, and the population at risk. The investigations show that the release of gas in the event of damage to the one-inch outlet valve of the tank can be lethal up to a radius of ۲ km, effective up to a radius of ۶.۲ km, and felt up to ۱۰ km. Considering the possibility of an accident and the location of the station in the direction of the wind, it is possible to harm a large number of citizens living within a ۵ km radius of the station. Effective measures are therefore needed to inform the local population, raise awareness among employees and emergency services, install a suitable scrubber, and increase the safety level of the station.

کلمات کلیدی:
Danger zone, Release rate, chlorine gas, Abadan station

صفحه اختصاصی مقاله و دریافت فایل کامل: https://civilica.com/doc/1832041/