Islanding Detection in distribution system with penetration of VSIbased DGs using wavelet energy spectrum analysis

Publish Year: 1392
نوع سند: مقاله کنفرانسی
زبان: English
View: 1,154

This Paper With 5 Page And PDF Format Ready To Download

  • Certificate
  • من نویسنده این مقاله هستم

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این Paper:

شناسه ملی سند علمی:

ICREDG03_082

تاریخ نمایه سازی: 9 تیر 1392

Abstract:

This paper presents a new fast and reliable method for islanding detection based on measuring the utility current signal processed by discrete wavelet transform. This signal ismeasured before the main circuit breaker and its feature extracted by discrete wavelet transform. This feature is waveletcoefficient energy and distinguishes the islanding conditions from non-islanding ones. Because of changing in measuring point of current signal from point of common coupling in traditional methods to before the main circuit breaker in proposed method, and using its transient data, this new methoddetects the islanding conditions faster than the other methods. The proposed method is useful for islanding detection in the networks with multiple distributed generations. To confirm the accuracy of this method, the method has been validated through several scenarios. Simulation results supported the robustness of the proposed method for the application considered

Authors

M. R. Vatani

Electrical Engineering Department, Amirkabir University of Technology Tehran, Iran

مراجع و منابع این Paper:

لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :
  • R. Lasseter. White Paper on Integration of Distributed Energy Re ...
  • _ _ _ _ [Online]. Availabe ...
  • _ _ Power Engineering Society Winter Meeting, 2001, vol. 1, ...
  • Interconnecting Distributed Resources With Electric Power Systems, IEEE Std. 1547-2003, ...
  • H. H. Zeineldin, J. L. Kirtley, "Islanding Operation of Inverter ...
  • The feature values in this scenario for five level of ...
  • 5x10-4 0.0017 O.0034 0.0068 ...
  • Phenomena of Utility Interactive PV Systems", Solar Energy Materials and ...
  • Laboratories report _ 1939, Sandia National [15] _ _ _ ...
  • _ _ _ _ _ _ Unit, " Power Electronics, ...
  • Y Jun, C.P.Diduch, C.Liucheng _ "Islanding Detection Using Proportional Power ...
  • _ _ _ Detection no.2, pp.764- 771, April 2009. ...
  • L. Safavian, W. Kinsner, H. Turanli, "A probabilistic approach to ...
  • _ G.Gharehpetian, M. Noroozian, "A new fast and reliable method ...
  • W. Xu, G. Zhang, C. Li, W. Wang, G. Wang, ...
  • _ H. Zeineldin, E. El-Saadany, M. Salama, "Impact of DG ...
  • W.Freitas, Z.Huang, W.Xu, "A Practical Method for Assessing the Effectivenese ...
  • _ Fielding, _ utility grid supply for a dispersed storage ...
  • H. Kobayashi, K. Takigawa, E. Hashimoto, "Method for Preventing Islanding ...
  • S. I. Jang, and K. H. Kim, _ islanding detection ...
  • G. A. Smith, P. A. Omions, and D. G. Infield, ...
  • S. Yuyama, T. Ichinose, K. Kimoto, T. Itami, T. Ambo, ...
  • نمایش کامل مراجع