DETECTING MECHANICAL MOVEMENT IN THE WINDING OF TRANSFORMERS USING FREQUENCY RESPONSE ANALYSIS

Publish Year: 1383
نوع سند: مقاله کنفرانسی
زبان: English
View: 1,963

This Paper With 10 Page And PDF Format Ready To Download

  • Certificate
  • من نویسنده این مقاله هستم

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این Paper:

شناسه ملی سند علمی:

PSC19_251

تاریخ نمایه سازی: 12 آذر 1385

Abstract:

Condition monitoring of power transformers is of paramount importance for reliable operation of the power system. The transformers in service encounter failures due to several operational stresses e.g. electrical, mechanical, chemical, thermal, and environmental. The assessment of the condition of a transformer winding ,which is suspected of having a short-circuit damage, using conventional tests such as winding resistance, magnetizing current, or insulation resistance is quite difficult. These tests are effective when the damage is severe in nature. On the other hand, the visual inspection of windings despite being an effective proposition but necessitates the removal of oil from the tank and thus requires a longer shutdown. Therefore, for diagnosing incipient electrical faults in the transformer winding, the Frequency Response Analysis (FRA) Technique is found to be the most effective tool for reliable detection of mechanical faults such as winding movement, loss of clamping pressure and disc movement. Historical data are, undoubtedly, the best reference to be used as comparison for FRA measurements. However, it is not practically easy to get historical data due to constraints of outages. This paper comes up with the proposed criteria on how to choose reference FRA measurements for power transformers in the absence of historical data. Case studies were also carried out on healthy power transformers that have no historical FRA measurements to show the effectiveness of the proposed criteria.

Authors

Muhammad Azizi Abdul Rahman

Department of Engineering Services & Logistic, Distribution Division, TNB Malaysia

Ghosh

Universiti Tenaga Nasional, Malaysia

مراجع و منابع این Paper:

لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :
  • http ://grouper.iee .org/group s/transformers /in fo / FRA/FRA_T utori al_Charles_ ...
  • http ://www _ doble _ c om/pro ducts/S FRA_Ce nter/c ...
  • S. Birlasekaran, F. Fetherston, Off/On-Line FRA Condition Monitoring Technique For ...
  • S. A. Ryder, Frequency Response Analysis for Diagnostic Testing of ...
  • S. A. Ryder, Diagnosing Transformer Faults Using Frequency Response Analysis, ...
  • S. A. Ryder, Metlod For Comparing Frequency Response Analysis Meas ...
  • http ://www .haefely. c om/l iterature/p df/scie ntific/e1 -97.pdf ...
  • نمایش کامل مراجع