Improvement in the Synchronization Process of the Voltage-Sourced Converters Connected to the Grid by PLL in order to Detect and Block the Double Frequency Disturbance Term

Publish Year: 1392
نوع سند: مقاله کنفرانسی
زبان: English
View: 1,512

This Paper With 11 Page And PDF Format Ready To Download

  • Certificate
  • من نویسنده این مقاله هستم

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این Paper:

شناسه ملی سند علمی:

ICEEE05_273

تاریخ نمایه سازی: 3 آذر 1392

Abstract:

PLL Structures have many applications in power system engineering. When required the synchronous performance of Voltage Sourced Converter (VSC) with Grid, such as wind power generation system, active filters, HVDC transmission lines and FACTS devices, the most common method for accurate estimation of frequency of network, is to use a PLL. However, problems such as grid disturbances due to noise, voltage unbalances, lack of coordination, changes in grid frequency and harmonics can produce a frequency disturbance, twice the grid frequency and disturbed PLL and also the control system connected to it. In this paper, common structures of PLL is introduced. After that, unbalance and disturbance in the three phase input of PLL is studied. Then for idea and invention in PLL, a new control method based on predictive control technique is used in the control strategy of converter. Furthermore, the use of type III controller in PLL to ensure optimal performance in various conditions is proposed in this paper. How to set the parameters of the proposed controller is described by the Bode stability criterion. Conducting simulations to evaluate the performance of the proposed method is done in PSIM software. According to the proposed method and the result observed, the double frequency disturbance term is weakened and also the transient state is improved. In this article as an idea and innovation, we use a new predictive controller named Deadbeat in control circuit of PWM voltage sourced converter and a type-3 controller was used as Loop filter in PLL control circuit and the simulations were performed. Results were shown that the proposed controller is more sensitive to the problem. In the proposed method, in addition to weaken the double frequency disturbance term, in practice it is very easy to implement. In addition simulations were performed on the change of grid frequency. Simulation results confirmed the good performance of the proposed method. Some of the benefits of the proposed controller is expressed as follows: Good performance and provide the appropriate PM. While it is not so complicated. Not complicated means that it will be easily led to construction. This controller have 3 capacitors and 3 resistors with an op-amp. It is easy to implement in analog. With zero steady state error of the step, ramp and parabolic input.

Authors

HamidReza Mahdian

Arak Science and Research branch, Islamic Azad University, Arak, Iran

MohammadReza Hashemi

Arak Science and Research branch, Islamic Azad University, Arak, Iran

Ali Asghar Ghadimi

Arak University, Faculty of Electrical Engineering, Arak, Iran

مراجع و منابع این Paper:

لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :
  • Amirnaser Yazdani and Reza Iravani, _ 'Voltage -Sourced Converters in ...
  • Remus Teodorescu, Marco Lisere and Pedro Rodriguez, "Grid Converters For ...
  • نمایش کامل مراجع