An Approach to Determine the Optimal Location ofThyristor-controlled Phase Shifting Transformer toImprove Transient Stability in Electric Power System
Publish place: The first national conference on electrical engineering of Islamic Azad University, Langarud branch
Publish Year: 1393
نوع سند: مقاله کنفرانسی
زبان: English
View: 456
This Paper With 5 Page And PDF Format Ready To Download
- Certificate
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
ICEES01_056
تاریخ نمایه سازی: 16 اسفند 1394
Abstract:
This paper presents an approach to determine theoptimal location of thyristor-controlled phase shiftingtransformer (TCPST) for enhancing the transient stability ofpower system. TCPSTs are a cost-effective means to ensurereliable andefficient power flow control in overloadedtransmission lines. This feature leads toreduction of the rotorangle separation of synchronous generators during disturbance occurrence which, results in an improvement of transientstability of network. To select the optimal location of TCPST,the angular separation of the rotors of generators in differentpositions of TCPST installation was calculated. Implementationof the proposed method on WSCC 9-bus and New England 39-bus test system shows the good efficiency of this method forimproving transient stability. The results show that installationof TCPST in proper possessiondecreases the angular separationof the rotors of generators, which effectively improves thesystem’s transient stability
Authors
Mohammad Azimi Ashpazi
University of TabrizTabriz, Iran
مراجع و منابع این Paper:
لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :