Effect of Inlet Air Cooling by Absorption Chiller and Fog Cooling Method on Gas Turbine Performance

Publish Year: 1386
نوع سند: مقاله کنفرانسی
زبان: English
View: 1,838

This Paper With 12 Page And PDF Format Ready To Download

  • Certificate
  • من نویسنده این مقاله هستم

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این Paper:

شناسه ملی سند علمی:

ICHEC05_333

تاریخ نمایه سازی: 7 بهمن 1386

Abstract:

Gas turbine performances are directly related to site conditions. In recent years, inlet air cooling systems have been introduced to control air temperature at compressor inlet, resulting in an increase in power and efficiency. In this paper, the dependence of outside conditions for a simple gas turbine is studied, using absorption chiller and fog cooling method as inlet air cooling systems. A computer program in FORTRAN environment developed for this purpose with simultaneously calculations. We used, as case study, a simple plant equipped with one frame B gas turbine. This program is developed to consider effect of blade cooling on gas turbine performance. Effect of off-design condition on gas turbine performance exactly is considered. It was found that inlet air cooling with absorption chiller has great positive influence on power and less on efficiency of the gas turbine plant. Fog cooling method is more suitable for hot and dry conditions and has great positive influence on power and efficiency but in humid places, it is not applicable.

Authors

Mohammad Javad Shafaei

Department of petroleum Engineering Petroleum University of Technology

Mahmoud khoshbakht

Associated Professor Department of Petroleum engineering Petroleum University of Technology

مراجع و منابع این Paper:

لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :
  • Rolf H. Kehlhofer, 1999, "Combined cycle Gas and Steam Turbine ...
  • M. Chaker, C.B. Meher-Homji, T. Mee III, A. Nichelson, 2003, ...
  • M .M.Alhamzy, T.S.H.Najjar, 2004, ،، Augmentati _ of turbine performance ...
  • M. Ameri, S.H.Hejazi, 2004, ، The study of capacity enhancement ...
  • for the economic evaluation of Methodology؛، , 2004 [5]. R. ...
  • C.B. Meher-Homji, M. Chaker, 2002, 4، Gas turbine power augmentation ...
  • M. Chaker, C.B. Meher-Homji, 2002, *Efficiency improvement and power augmentation ...
  • Fuel to air mole fraction ...
  • John S. Anderpont, 2000, ،Combustion turbine inlet aircooling benefits, technology ...
  • R. Yokohama, K. Ito, 2000, ،Evaluation of operational performance of ...
  • M.El-Masri, 1987, "Exergy Analysis of Combined Cycles: Part 1 ", ...
  • A.Tabari , H.Khaledi and A.H.Banisi , 2006 , " Comparative ...
  • T.S.Kim and S.T, Ro _ 1 995 , "Comparitive Evaluation ...
  • D.E.Muir , H.I.H. S aravanamutto and D.J.Marshall _ 1989, " ...
  • Q .Z .Al-Hamdan and M.S.Y.Ebaid , 2006 , " Modeling ...
  • G.Jones , P.Pilidis and B.Curnock _ 2001 , "Compressor Charactristics ...
  • J.Kurzke , 2003, "Model Based Gas Turbine Parameter Corrections _ ...
  • J.Kurzke , 1995 _ "Advanced User Friendly Gas Tuebine Performance ...
  • J.Kurzke , 2002 , "Performance Modeling Methodology : Efficiency Definitions ...
  • H.Cohen , G.F.C. Rogers , H.I.H. S aravanamutto O _ ...
  • Philip P.Walsh , 2004, ،، Gas Turbine Performance 4 , ...
  • khaledi, 2004 _ Modeling and optimization of advanced combined cycle ...
  • نمایش کامل مراجع