Dynamic Calculation of Leakage Current and Electric Field of Distribution polymeric insulator under pollution layer

Publish Year: 1391
نوع سند: مقاله کنفرانسی
زبان: English
View: 276

This Paper With 6 Page And PDF Format Ready To Download

  • Certificate
  • من نویسنده این مقاله هستم

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این Paper:

شناسه ملی سند علمی:

ICOPTICP19_260

تاریخ نمایه سازی: 26 مرداد 1397

Abstract:

This paper presents two different methods to calculate the leakage current (LC) along a 20 kV silicone rubber (SiR) insulator surface. The first method which is based on field theory approach uses the Comsol software to compute the leakage current. The second method is based on Young model. Simulation approach was compared with the circuit theory model which developed by Young. This paper investigates the use of a dynamic pollution model to compute the electric field distribution along the leakage path. Also, the results show that the voltage and electric field distribution along silicone rubber insulator under wet polluted conditions are dependent on the insulator surface conductance and the magnitude of the E-field close to the energized end fitting is higher than the grounded end.

Authors

Mohammad Mehdi Khademi

Hormozgan electric power distribution company

abdolsaheb arjomand

Hormozgan electric power distribution company

hamid saedpanah

Hormozgan electric power distribution company