Achieving Green Airport Standards by Managing Indoor CO and CO۲ Levels at Domestic Terminal of Banyuwangi Airport
Publish Year: 1402
نوع سند: مقاله ژورنالی
زبان: English
View: 166
This Paper With 8 Page And PDF Format Ready To Download
- Certificate
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
JR_JEHSD-8-3_006
تاریخ نمایه سازی: 8 مهر 1402
Abstract:
Introduction: Green Airport is an airport development concept designed to be healthy. Excess levels of carbon monoxide (CO) and carbon dioxide (CO۲) in the room can cause discomfort in the form of headache, nausea, vomiting, vertigo, and feeling confused and weak. This study aimed to determine the implementation of CO and CO۲ control in rooms to achieve a green airport at Banyuwangi Airport.
Materials and Methods: In this descriptive study, the obtained data were compared with related regulations. The physical and chemical quality of indoor air was measured at ۸۵ points in three main rooms at risk using CO and CO۲ detectors. Control was done through observing and measuring ventilation and detection systems in the entire occupied space.
Results: The measurement results of CO and CO۲ levels have met the specified threshold value below ۲۹ ppm for CO and ۵۰۰۰ ppm for CO۲. Physical quality measurements have not met the requirements for indoor temperature above ۲۷.۱°C and humidity above ۶۰%. The assessment of ventilation aspects in the domestic terminal building of Banyuwangi Airport was achieved based on SNI ۰۳-۶۵۷۲-۲۰۰۱ received ۲۹ rooms or ۷۴.۳% of the rooms, ۱۰ rooms that do not fit the ventilation system are toilet.
Conclusion: The results of the assessment conducted show that there are still aspects that are not in accordance with the provisions of green buildings.
Keywords:
Authors
Boby Kurnia Aprilian
Health, Safety, Security, and Environmental (HSSE) Staff of Bhakti Husada Krikilan Hospital, Glenmore, Banyuwangi, Indonesia.
Muhammad Addin Rizaldi
Master Student of Environmental Health, Department of Environmental Health, Faculty of Public Health, Universitas Airlangga, Surabaya, Indonesia.
مراجع و منابع این Paper:
لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :