A New Protection Scheme for Stator Faults in Synchronous Generators
Publish place: 21th Iranian Conference on Electric Engineering
Publish Year: 1392
نوع سند: مقاله کنفرانسی
زبان: English
View: 1,469
This Paper With 7 Page And PDF Format Ready To Download
- Certificate
- من نویسنده این مقاله هستم
این Paper در بخشهای موضوعی زیر دسته بندی شده است:
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
ICEE21_833
تاریخ نمایه سازی: 27 مرداد 1392
Abstract:
A new voltage controlled overcurrent protection scheme is proposed which is a backup protection method for differential protection. This scheme whichis realized by fuzzy controllers is considered to be mounted beside a differential protection system, which operates in the cases that differential protection isunable to detect the fault. This novel protection scheme operates by adjusting the plug setting of the overcurrent relay that sends the trip signal to three-phase breaker.In the proposed method fault occurrences can be determined regardless of variations of voltage and currentof terminal in different working states of synchronous generator. This is done by measuring other variables than those used in conventional protection methods.To demonstrate the proposed method, a synchronous generator with internal fault model is used. Numerical simulations validate the functionality of this novel scheme under different conditions
Keywords:
Authors
Pouya Mahdavipour Vahdati
Iran University of Science and Technology, Tehran, Iran,
Arash Arjmandi
K.N.Toosi University, Tehran, Iran