Improving Safety of 20 kV Areal Lines using Fault Indicator and Fiberglass Crossarm
Publish place: National Conference of Technology, Energy & Data on Electrical & Computer Engineering
Publish Year: 1394
نوع سند: مقاله کنفرانسی
زبان: English
View: 912
This Paper With 8 Page And PDF Format Ready To Download
- Certificate
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
TEDECE01_590
تاریخ نمایه سازی: 30 آبان 1394
Abstract:
Twenty kV feeders of earth fault relay and high-voltage relays are installed on breakers to protect feeders against faults; however, a 20 kV back flow phase of wire sometimes ruptures and falls on the ground and the existing relays are unable to detect it. Moreover, distance and differential relay will not increase undistributed energy. This article presents a new method to detect wire rupture using the existing relays. By installing a fault indicator (a commutation sensor installed in the end of the main and branches lines), a feedback of voltage and feeder’s current status is created and if a wire ruptures, a breaker cut command will be issued and it will prevent many casualties.
Keywords:
Authors
Alireza Khajoee Ravari
Azad University of Kerman, iran
Hadi Zayandeh Roudi
Azad University of Kerman, iran
Ali Khajehzadeh
Azad University of Kerman, iran
مراجع و منابع این Paper:
لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :