Elimination of Harmonics in a Multilevel Inverter Connected to DG Using the Hybrid PSOGA Algorithm
Publish place: ششمین کنفرانس انرژی های تجدید پذیر و تولید پراکنده ایران
Publish Year: 1396
نوع سند: مقاله کنفرانسی
زبان: English
View: 344
This Paper With 7 Page And PDF Format Ready To Download
- Certificate
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
ICREDG06_175
تاریخ نمایه سازی: 1 دی 1397
Abstract:
Distributed generation (DG) becomes more important day by day due to environmental condition so implementation of convertors that interfacing DC output of DG to AC main grid is inevitable. This paper presents an optimal solution for a selective harmonic elimination pulse width modulated (SHE-PWM) technique suitable for a high power inverter used in constant frequency utility applications. The two main objective of this study are the elimination of specified low order harmonics and achieve to appropriate value of first component of output voltage. This paper applies a hybrid PSOGA algorithm that combines operators of GA such as cross over and mutation with PSO algorithm to solve SHE equations, resulting in desired ac output waveform. It is shown that for a range of the modulation index the switching angles can be chosen to achieve minimum total harmonic distortion (THD). In the following, simulation results are presented for 9-level and 11-level MultiLevel Inverter (MLI).
Keywords:
Authors
Saeed ghahramanian
National Iranian Gas Transmission Company-dist۸ Maku Iran
Sadegh Akbarpour
National Iranian Gas Transmission Company-dist۸ Maku, Iran
Amir Kheirani
National Iranian Gas Transmission Company-dist۸ Maku, Iran