Fast Grid Voltage Synchronization Using Modified FLL in Single-Phase Grid-Connected Power Systems
Publish Year: 1400
نوع سند: مقاله ژورنالی
زبان: English
View: 265
This Paper With 8 Page And PDF Format Ready To Download
- Certificate
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
JR_IJE-34-6_006
تاریخ نمایه سازی: 12 خرداد 1400
Abstract:
One of the critical components for the efficient operation of single-phase grid-connected converters is the synchronization unit. This paper presents a fast and adaptive phase-locked loop (PLL) structure that ameliorates the dynamic response of the estimated frequency and amplitude for grid-connected single-phase power systems. The second-order generalized integrator (SOGI) with a novel frequency-locked loop (FLL) is utilized which contains a DC offset rejection loop. The proposed method not only eliminates the transient response of the estimated frequency which is produced by FLL in grid voltage phase angle jumps, but also improves the PLL dynamic characteristics. The whole system has been simulated in MATLAB Simulink environment where a very small settling time for the estimated frequency of the FLL has been achieved. Therefore, it will improve the whole dynamic parameters of the system. Based on the simulation results, the settling time for the estimated frequency and amplitude are ۲۲ ms and ۱۰ ms, respectively.
Keywords:
Authors
H. Hassanpour
Faculty of Electrical Engineering, K. N. Toosi University of Technology, Tehran, Iran
M. Ehsanian
Faculty of Electrical Engineering, K. N. Toosi University of Technology, Tehran, Iran
مراجع و منابع این Paper:
لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :