Ground Coupled Heat Pump Design for Tafila Climate
Publish Year: 1396
نوع سند: مقاله ژورنالی
زبان: English
View: 215
This Paper With 5 Page And PDF Format Ready To Download
- Certificate
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
JR_APRIE-4-3_003
تاریخ نمایه سازی: 2 دی 1400
Abstract:
This work represents a theoretical investigation of a ground coupled heat pump system that is used for domestic heating and cooling purposes of a typical residential house in Tafilah-Jordan. The system is designed to provide heating and cooling loads of ۷.۳۹, ۷.۲۷ KW respectively. The designed system consists of a ground buried heat exchanger (۱.۵m depth, ۶.۵m length, and ۲.۲cm diameter), indoor heat exchanger, and a ۲ HP compressor. The system has been analyzed economically and it was found that the ground coupled heat pump system reduces energy consumption and has a payback period for of ۱.۵ years.
Keywords:
Authors
Emran. M. Ataykah
Department of Mechanical Engineering, Tafila Technical University, Jordan.
مراجع و منابع این Paper:
لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :