Nozzle Displacement Effects on Two-Phase Ejector Performance: An Experimental Study

Publish Year: 1397
نوع سند: مقاله ژورنالی
زبان: English
View: 140

This Paper With 8 Page And PDF Format Ready To Download

  • Certificate
  • من نویسنده این مقاله هستم

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این Paper:

شناسه ملی سند علمی:

JR_JAFM-11-4_001

تاریخ نمایه سازی: 18 دی 1400

Abstract:

Experimental results of two-phase ejector operation with refrigerant R۱۳۴a as working fluid are presented in this paper. The tests carried out allowed evaluating the influence of the primary nozzle position in the mixing chamber and of operating conditions such as the thermodynamic state of the fluid at the inlet and outlet of the ejector. Various positions of the primary nozzle were tested and the operating conditions ranges were: primary inlet pressure ۸.۸-۱۴.۹ bars, subcooling ۰.۲-۵ °C and ejector outlet pressure ۳.۷-۴.۷ bars. The tests have shown an optimal position of the primary nozzle (NXP=۳۸.۱ mm) in the ejector but this position was not very sensitive to operational conditions. The performance of the ejector dropped sharply when the nozzle was placed right at the inlet of the constant-area section in the mixing chamber. Pressures at the primary inlet and outlet had a limited impact on the entrainment ratio (

Authors

K. Ameur

Canmet ENERGY, Natural Resources Canada, Varennes, Qc, J۳X۱S۶, Canada

Z. Aidoun

Canmet ENERGY, Natural Resources Canada, Varennes, Qc, J۳X۱S۶, Canada