سیویلیکا را در شبکه های اجتماعی دنبال نمایید.

Numerical Simulations on Visibility and Temperature in a Car Park of a Commercial Building

Publish Year: 1402
Type: Conference paper
Language: English
View: 240

This Paper With 7 Page And PDF Format Ready To Download

Export:

Link to this Paper:

Document National Code:

MEMCONF10_036

Index date: 11 September 2023

Numerical Simulations on Visibility and Temperature in a Car Park of a Commercial Building abstract

The study of temperature and visibility in the parking of the commercial complex was done by Fire Dynamic Simulator code with various fire accident. Specification fire of parking were obtained in different fan system conditions. Temperature and visibility of a stairwell on various conditions were contrasted. The values were obtained at a height of 1.6m. The results showed that in the first state, temperature and visibility reached 80°C and 1 meters in 1200s after the fire, respectively. In the second state, visibility reached 6.34m in 1200s, which was 6.34 times better than the first state. The temperature also decreased to 51.11°C in 1200s. The temperature improved by 36.19% compared to the first state. In the third state, after 1200s, the temperature decreased 44.72°C. In the third state, the visibility was 15.59m, which improved 15.59 times the first state.

Numerical Simulations on Visibility and Temperature in a Car Park of a Commercial Building Keywords:

Numerical Simulations on Visibility and Temperature in a Car Park of a Commercial Building authors

Fatemeh Behbahani

Department of Mechanical Engineering, Ahvaz Branch, Islamic Azad University, Ahvaz, Iran

Mahdi Hamzei

Department of Mechanical Engineering, Ahvaz Branch, Islamic Azad University, Ahvaz, Iran

Zahra Mehrdoost

Department of Mechanical Engineering, Ahvaz Branch, Islamic Azad University, Ahvaz, Iran

Mohammad Moghiman

Department of Mechanical Engineering, Ferdowsi University, Mashhad, Iran