Fault Location for Long Transmission Lines Using Two-Terminal Unsynchronized Data

Publish Year: 1391
نوع سند: مقاله کنفرانسی
زبان: English
View: 1,786

This Paper With 6 Page And PDF Format Ready To Download

  • Certificate
  • من نویسنده این مقاله هستم

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این Paper:

شناسه ملی سند علمی:

ISCEE15_285

تاریخ نمایه سازی: 3 آذر 1391

Abstract:

This paper presents a new two-terminal fault location algorithm, which takes into account the distributed parameter line model. This algorithm utilizesunsynchronized measurements of voltages and currents from two ends of a line to estimate the location of the fault. The proposed algorithm is independent of faultresistance and does not require any knowledge of source impedance. Voltages of the two terminals in the fault time are only equivalent at the fault location. Therefore, to find the accurate location of fault, an objective function is defined on the difference of the voltages of the two terminals in the fault time and then it is minimized. Solving this optimization problem, the location of fault is determined.The developed fault location algorithm has been thoroughly tested using signals of PSCAD/EMTDC simulations of faults on a transmission line. The presented evaluation shows the validity of our proposed algorithm and its high accuracy

Authors

Samaneh Raaee

Islamic Azad University, saveh branch, Iran

Mostafa Sedighizadeh

Assistant Professor, Imam Khomeini International University

Mostafa Yousefi Ramandi

Msc Student, Imam Khomeini International University

مراجع و منابع این Paper:

لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :