Coordination of adaptive distance protection in transmission and wind farm collector lines under resistive fault conditions
Publish place: International Journal of Industrial Electronics, Control and Optimization، Vol: 3، Issue: 3
Publish Year: 1399
نوع سند: مقاله ژورنالی
زبان: English
View: 104
This Paper With 12 Page And PDF Format Ready To Download
- Certificate
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
JR_IECO-3-3_002
تاریخ نمایه سازی: 20 تیر 1401
Abstract:
Distance relays calculate the path impedance between the fault point and the relay location by sampling the voltage and current at the relay location. By using the ratio of the impedance estimated by the relay to the impedance of the line where the relay is installed, the location of the fault can be estimated by a distance relay. However, several factors influence the estimated impedance and proper operation of distance relays. The most important of these factors is the resistive fault occurrence, which results in an increase in the impedance and deviation of the impedance estimated by the relay as well as causes relay under-reach. Therefore, in the present study, an adaptive method is proposed to modify the protection zones of distance relays settings under different operating conditions and resistive fault occurrence. Furthermore, the adaptive distance protection of transmission lines, wind farm collector lines and the protection coordination of the relays in these lines are investigated. In this method, an adaptive coefficient is added to the conventional characteristics of distance relays to improve the accuracy and coordination. The proposed adaptive method can also maintain the coordination of different protection zones of primary and backup relay pairs. In addition to analytical verification, the numerical results obtained from simulation show the efficiency of the proposed method. The proposed method is implemented on a power system with transmission lines and wind farms and simulated in MATLAB/Simulink environment.
Keywords:
Authors
Jamshid Barati
Department of Electrical Engineering, Shahid Chamran University, Ahvaz, Iran
Seidghodratollah Seifossadat
Department of Electrical Engineering, Shahid Chamran University, Ahvaz, Iran
Mahmood Joorabian
Department of Electrical Engineering, Faculty of Engineering, Shahid Chamran University of Ahvaz, Ahvaz, Iran
مراجع و منابع این Paper:
لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :