A Complete Excitation-Shaft-Bearing Model to Overcome The Shaft Induced Voltage And Bearing Current
Publish Year: 1389
نوع سند: مقاله کنفرانسی
زبان: English
View: 2,028
This Paper With 5 Page And PDF Format Ready To Download
- Certificate
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
PEDSTC02_037
تاریخ نمایه سازی: 21 تیر 1391
Abstract:
This paper proposes a complete distributed model for investigating the induced shaft voltage and bearing current in turbo generators due to the interaction with the static excitation systems. This undesirable voltage affects the insulations gradually, lowering the life expectancy of the whole system. If the shaft voltage exceeds the dielectric breakdown voltage level of the lubricating grease film in journal bearings, an electrical discharge current flows through the bearings. In order to inspect the shaft voltage, a passive filter is proposed to overcome the stated issue. Both the proposed model and the passive filtering technique are simulated with SIMULINK, and discussed in detail to confirm the presence of the bearing current and shaft voltage.
Keywords:
Authors
reza Kazemi Golkhandan
Department of Electrical Engineering K. N. Toosi University of Technology Tehran,Iran
mohammad Tavakoli Bina
Department of Electrical Engineering K. N. Toosi University of Technology Tehran,Iran
masoud Aliakbar Golkar
Department of Electrical Engineering K. N. Toosi University of Technology Tehran,Iran
mohsen jokar
MAPNA E&C Co.(MECO) Karaj,Iran