Power Disturbance Characterization
Publish place: Monthly Oil & Energy، Vol: 4، Issue: 34
Publish Year: 1388
نوع سند: مقاله ژورنالی
زبان: English
View: 422
This Paper With 10 Page And PDF Format Ready To Download
- Certificate
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
JR_OIL-4-34_005
تاریخ نمایه سازی: 22 فروردین 1397
Abstract:
Short-term ac voltage disturbances can be classified into four major categories, as illustrated in Figure 10.1.The categories are defined according to peak value and duration:● Voltage surge: An increase of l0 to 35% above the nominal line voltage for a period of 16 ms to 30 s.● Voltage sag: A decrease of 10 to 35% below the nominal line voltage for a period of 16 ms to 30 s.● Transient disturbance: A voltage pulse of high energy and short duration impressed upon the ac waveform. The overvoltage pulse can be 1 to 100 times the nominal ac potential and can last up to 15 ms. Rise times measure in the nanosecond range.R ) (. ,35*)1 ,5#(. ,,/*.#)(95 5 , - 5.)54 ,)50)&. ! 5 of the ac power-line potential, lasting from 33 to 133 ms. Longer-duration interruptions are considered power outages