Digital Distance Protection For Cable Transmission Line
Publish place: 05th International Power System Conference
Publish Year: 1369
Type: Conference paper
Language: English
View: 2,004
This Paper With 8 Page And PDF Format Ready To Download
- Certificate
- I'm the author of the paper
Export:
Document National Code:
PSC05_003
Index date: 16 August 2007
Digital Distance Protection For Cable Transmission Line abstract
As increasing the under ground cable length, the harmonic content ratio of low harmonic orders, such as 2nd 3rd harmonic , in the transient current and voltage on the fault occurrence , have been remarkable . the phenomena causes a big problem for the line protection system especially for distance protection of the existing type. To cope with above, new distance protectionrelay using digital micro-processor technique has been developed.
The reactance and resistance from relay to fault point are directly calculated by using high sampling ratio of 15 electrical degrees and high performance digital filter which eliminates the 3rd, and higher harmonic components.
To confirm the actual operation of the developed relay with heavely distorted waves, the relay has been extensively tested by using current and voltage converted from EMTP (Electro-Magnetic Transient Program) simulation output data of large capacitive system.
Digital Distance Protection For Cable Transmission Line authors
مراجع و منابع این Paper:
لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :