Ferroresonance Suppression Circuit in Coupling Capacitive Voltage Transformer Using Power Electronic Devices and Surge Arrester
Publish place: 22nd International Power System Conference
Publish Year: 1386
Type: Conference paper
Language: English
View: 3,309
This Paper With 6 Page And PDF Format Ready To Download
- Certificate
- I'm the author of the paper
Export:
Document National Code:
PSC22_216
Index date: 5 May 2007
Ferroresonance Suppression Circuit in Coupling Capacitive Voltage Transformer Using Power Electronic Devices and Surge Arrester abstract
To avoid or damp out ferroresonance in coupling capacitive voltage transformer (CCVT), a ferroresonance damping method have been proposed and evaluated in these instruments.
In this technique, by using power electronic devices, a damping resistance is switched to secondary side of the system transformer during dangerous oscillations. This technique leads to important cost and damping time reductions when compared with conventional alternatives.
Additional devices such as surge arresters may be added to improve the performance of the FSC. The prediction of ferroresonance is achieved
by detailed modeling using a digital computer transient analysis program such as the EMTP/ATP.
Ferroresonance Suppression Circuit in Coupling Capacitive Voltage Transformer Using Power Electronic Devices and Surge Arrester Keywords:
Ferroresonance , Coupling Capacitive Voltage Transformer , Ferroresonance Suppression Circuit , EMTP/ ATP
Ferroresonance Suppression Circuit in Coupling Capacitive Voltage Transformer Using Power Electronic Devices and Surge Arrester authors
مراجع و منابع این Paper:
لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :