Using Static Frequency Inverters ForDistribution Transformer Tests abstract

In high voltage systems, usual method of making a wave with a frequency over 50 Hz that has high power is interconnecting a motor and a generator with nominal frequency over 50Hz, like 100Hz or 150Hz; but for distribution transformers' routine test, it is not economical to construct an experimental setup with a motor and generator that would be expensive. Nowadays with power electronics instruments some cheap solutions are available, like power frequency inverters that transmit power from the 50Hz network to over 50Hz sinusoidal wave as output. This paper eviews a procedure of design and construction a test circuit for induced voltage tests, loss measurements and applied voltage tests based according to IEC 60076-3, based on a three phase power frequency inverter works at a frequency range 0…200 Hz. This system strongly needs a compensation unit, adaptation transformer, and a HV passive filter for the induced voltage tests; also with this circuit partial discharge easurements are possible. There are no particular inductors have been designed for filtering the harmonics, therefore experimental equipments and test object have been used to perform an appropriate filter.

Using Static Frequency Inverters ForDistribution Transformer Tests Keywords:

Static frequency inverter , filter , Induced voltage test , Total harmonic distortion (THD)

Using Static Frequency Inverters ForDistribution Transformer Tests authors

Mohseni

School of Electrical & Computer Eng., University of Tehran

Shaygani-Akmal

School of Electrical & Computer Eng., University of Tehran

Jadidian

School of Electrical & Computer Eng., University of Tehran

Hashemi

School of Electrical & Computer Eng., University of Tehran

مراجع و منابع این Paper:

لیست زیر مراجع و منابع استفاده شده در این Paper را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود Paper لینک شده اند :
IEC 60076-3 Power Tran _ formers-part3 : Insulation Levels, dielectric ...
IEEE Guide for Induced Voltage test and Partial Discharge Measurement ...
A. Thiede, D. Martin, «Power Frequency inverters for High Voltage ...
A. Winter, P. Coors, U. Stephen, *"A Mobile Transformer Test ...
نمایش کامل مراجع